+27 (0)11 568 0236 sking@acontrols.co.za

FCU ControllerGlobal Control 5 provides advanced building automation solutions developed by highly experienced specialists. iSMA Controllers including the iSMA – B – FCU controller is equipped with open communication protocols: Modbus ASCII/RTU and BACnet MSTP. By providing a large number of inputs and outputs, these controllers are able to communicate with a large number of other devices.

The iSMA-B-FCU is able to support the most popular types of FCU’s straight out of the box. With its dedicated DIP-switches, parameters can be adjusted as required.

Key Features of the iSMA – B – FCU Controller

  • Pre-loaded universal application
  • Support 2-pipe or 4-pipe systems
  • Application adjustable by dedicated DIP-switch
  • Programming in real-time
  • Addressing from 0 to 255 by DIP-switch
  • Built-in 18 Inputs/Outputs • Sedona Framework 1.2 support
  • Fast processor with ARM core
  • Modbus ASCII/RTU or BACnet MSTP for connecting to higher level system
  • 2x RJ12 (1x RS485) for connecting wall panels, external devices communicating in Modbus ASCII/RTU
  • Built-in 24 V AC for an external equipment (version 230 V AC).

Inputs

  • 4x Special Input – voltage, resistance, dry contact
  • 4x Digital Input – dry contact Outputs
  • 3x Digital Output 6 A (Fan Speed)
  • 1x Digital Output 10 A (electric heater)
  • 1x Digital Output 6 A (cooling actuator)
  • 2x Triac 0,5 A @ 230 V AC or 0,5 A/0,3 A* @ 24 V AC (heating and cooling, actuators)
  • 3x Analog Outputs 0-10 V DC (heating, cooling actuators and Fan Speed) Platform

ARM Cortex-M4 Power supply

  • 230 V AC or 24 V AC Communication
  • Interface RS485 half-duplex
  • Up to 128 devices on the bus

Protocols:

  • Modbus or BACnet
  • Baud rate: 4800 to 115200 bps

Housing Dimension

  • 123,6 x 136,6 x 54,5 mm, (123,6 x 171,2 x 54,9 mm) with plastic cover for terminals

Construction

  • plastic, self-extinguishing (PC/ABS)
  • DIN rail mounting DIN (DIN EN 50022 norm)
  • Cooling internal air circulation Environment
  • Operating temperature -10°C to 50°C
  • Storage temperature -40°C to 85°C
  • Relative humidity 5% to 95%, non-condensing
  • Ingress Protection Rating IP40 – for indoor installation